Load audio files yourself over the rear Micro USB port. WAV and MP3 supported
AMR-SPK-5-24-RS485 ·
RS485 · 12–36 V supply · 90 dB
· View product
Folder
0 is stop · 1–255
map to folders AW001–AW255 in the box
Load audio files yourself over the rear Micro USB port. WAV and MP3 supported
Volume
20
🔴 The device address is fixed at 1 and users cannot change it
A different value must be requested when ordering
This means You cannot put two of these on one RS485 bus Duplicate addresses answer simultaneously and neither reply is readable
For several points — specify addresses when ordering · separate buses · or add external speakers to a single box
This means You cannot put two of these on one RS485 bus Duplicate addresses answer simultaneously and neither reply is readable
For several points — specify addresses when ordering · separate buses · or add external speakers to a single box
0–28 (29 steps) — move the slider, then play again to apply
The box also has a volume knob on the back The two multiply With the knob turned down, commanding 28 is still quiet
The box also has a volume knob on the back The two multiply With the knob turned down, commanding 28 is still quiet
Quick play
Press to play that folder immediately at the set volume —
useful for finding which sound is in which folder
Communication log
This page uses vendor protocol, not Modbus
Frame layout
Here folder and volume go in one frame. Shorter than Modbus, but there is no read command so the "Read current values" button is not shown on this page
The box replies with byte 1 as
This family ships from the factory speaking this protocol by default. Use this page for units not ordered with Modbus or when the Modbus page gets no reply
Frame layout
01 · 51 · folder · 00 · volume · XOR · 02 integrity is a single XOR byte, not CRC16Here folder and volume go in one frame. Shorter than Modbus, but there is no read command so the "Read current values" button is not shown on this page
The box replies with byte 1 as
52 while the command we send is 51 They differ by one bit. If 51 comes back it means a cable echo, not the box replying — the tool warns youThis family ships from the factory speaking this protocol by default. Use this page for units not ordered with Modbus or when the Modbus page gets no reply